Secondary Injection Test Sets
AC-PRO® and AC-PRO-II Test Set®
The Model B-292 Secondary Injection Test Set is a
single-phase test set specifically designed for testing the
operation of the AC-PRO® and AC-PRO-II®
micro-controller based trip units manufactured by
Utility Relay Co.
The test set can test pick-up and time delays of the various
protection functions by driving current into the trip unit on the
secondary side of the CT circuit.
The test set will test 60, 50, 40 or 25 Hertz
AC-PRO® trip units. (The AC-PRO-II® can be set for either
50 Hertz or 60 Hertz).
The test set will test the AC-PRO® or AC-PRO-II® trip system
with the exception of the CTs and associated wiring harness.
Specifications:
- Dimensions: 22.1” L X 17.9” W X 10.4” H (560 mm L X 455mm W X 265mm H)
- 40 lbs (18.1 kg)
- Power Requirement: 120V, 3A
- Current Output: Single-phase, 0 -13A.
- Frequency: 25, 40, 50 or 60 Hertz.
- Current Display: 0.01 Amp Resolution
- Time Display: 0.01 Second Resolution
- Ultra high impact polypropylene shell.
- Chemical-Resistant
- Corrosion-Resistant
- Crush-Proof
AC-PRO-MP® and AC-PRO-MP-II Test Set®
The Model B-291-MP secondary injection test set is a single-phase test set specifically designed for testing the operation of the AC-PRO-MP family of microcontroller based trip units manufactured by Utility Relay Co.
The B-291-MP test set can test pick-up and time delays of the various protection functions by driving current into the AC-PRO-MP and AC-PRO-MP-II on the secondary side of the CT circuit.
This test set supports AC-PRO-MP and
AC-PRO-MP-II trip units programmed for 60 or 50 Hertz operation.
The test set will test the AC-PRO-MP and AC-PRO-MP-II trip system with the exception of the CTs and associated wiring harness.
Specifications:
- Dimensions: 22.1” L X 17.9” W X 10.4” H (560 mm L X 455mm W X 265mm H)
- 40 lbs (18.1 kg)
- Power Requirement: 120V, 3A
- Current Output: Single-phase, (up to 40xCT rating)
- Frequency: 50 or 60 Hertz.
- Current Display: 0.01 x CT Rating Resolution
- Time Display: 0.01 Second Resolution
- Ultra high impact polypropylene shell.
- Chemical-Resistant
- Corrosion-Resistant
- Crush-Proof
ZERO-Hertz Test Set®
The Model B-290 test set is specifically designed for
secondary injection testing of the ZERO-Hertz DC trip
unit.
Pick-up and multiple points on the time-current curves
can be quickly tested using this test set.
The test set can perform pick-up and time delay trip tests
for either the transducer inputs or the shunt inputs
depending on the model ZERO-Hertz DC trip unit.
The ZERO-Hertz DC trip unit is micro-controller based
and includes a 16-character liquid crystal display (LCD).
The trip unit provides the following protection functions:
- Long Time (LT)
- Short Time (ST)
- Instantaneous (I)
- Ground Fault (GF) (Transducer input only)
- Reverse Current (RC)
Specifications:
- Case Information: 8 x 8 x 16 inches
- Weight: 8 lbs (3.6 kg)
- Power Requirement: 120 VAC, 1 AMP
- Time Display: .001 second resolution LCD Time Display with Reset
- Transducer Input with current direction switch
- Shunt Input with current direction switch